LF866-LG-GPM 2 1/2
Discontinued
Part of the LF866 Series
Ordering Code: 0683150
UPC: 098268077797
2 1/2 In Lead Free DI Reduced Pressure Detector Backflow Preventer Assy, Epoxy Coated Using ArmorTek Technology, Less Shutoff, GPM Meter
This 2 1/2 inch lead free ductile iron MasterSeries (R) reduced pressure detector backflow preventer assembly is designed to prevent the reverse flow of fire protection substances and water of non-potable quality from being pumped or siphoned into the potable water supply due to backsiphonage and or backpressure in accordance with national plumbing codes and water authority requirements. It is ideal for protection in continuous pressure piping applications and at cross-connections identified as health hazards and from other contaminants found at the service line entrance. It is used primarily on fire sprinkler and standpipe systems requiring detection of unauthorized water use. This assembly without shutoff valves consists of a ductile iron body epoxy coated using ArmorTek coating technology for advanced corrosion resistance., replaceable stainless steel check seats, gallons per minute metered bypass, and ball valve test cocks.
Specifications | |
---|---|
ArmorTekTechnology | Yes |
BuyAmericanAct | NO |
EANUCCCode | 098268077797 |
MaximumTemperature-Fahrenheit | 140 |
MaximumWorkingPressure-BAR | 12.10 |
MaximumWorkingPressure-PSI | 175 |
MinimumTemperature-Celsius | 1.00 |
MinimumTemperature-Fahrenheit | 33 |
TrademarkName-Primary | MasterSeries(R) |